Range |
Insulation resistance |
Voltage
measurement |
500V |
1000V |
2500V |
5000V |
AC/DC V |
Measuring range |
0.0~99.9MΩ
100~999MΩ |
0.0~99.9MΩ
100~999MΩ
1.00~1.99GΩ |
0.0~99.9MΩ
100~999MΩ
1.00~9.99GΩ
10.0~99.9GΩ |
0.0~99.9MΩ
100~999MΩ
1.00~9.99GΩ
10.0~99.9GΩ
100~1000GΩ
(1TΩ) |
30~600V
AC/DC
[50/60Hz] |
Accuracy |
|±5%rdg |±3dgt |
|±5%rdg |±3dgt |
|±5%rdg |±3dgt |
|±5%rdg |±3dgt
|±20%(100GΩ or more) |
|±2%rdg |±3dgt |
Short Circuit Current |
1.3mA approx. |
------- |
Rated test Current |
1mA to 1.2mA
at 0.5MΩ load |
1mA to 1.2mA
at 1MΩ load |
1mA to 1.2mA
at 2.5MΩ load |
1mA to 1.2mA
at 5MΩ load |
------- |
Open circuit voltage |
500VDC
|
1000VDC
|
2500VDC
|
5000VDC
|
------- |
Maximum display |
999 Counts (1000 counts only at 1000GΩ) |
630 Counts |
Current consumption |
About 1000mA (During measurement) |
110mA approx. |
Withstand Voltage
Safety standard |
5320V AC for 5 seconds
IEC 61010-1 CAT.III 600V, pollution Degree 2 |
Power supply |
DC12V : R14×8 |
Dimensions |
205(L) × 152(W) × 94(D)mm |
Weight |
1.8kg approx. |
Accessories |
7165A (Line probe)
7224A (Earth cord)
7225A (Guard cord)
8019 (Hook type prod)
9159 (Carrying case [Hard])
LR14×8pcs (Alkaline battery size)
Instruction Manual, Calibration Certificate |
Optional |
7168A (Line probe with alligator clip)
7253 (Longer Line probe with alligator clip)
8302 (Adaptor for recorder) |