Wiring connections |
|
|
|
1P 2W, 1P 3W, 3P 3W, 3P 4W |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Measurements and parameters |
|
|
|
Voltage, Current, Frequency, Active power, Reactive power,
Apparent power, Active energy, Reactive energy, Apparent energy,
Power factor (cos θ), Neutral current, Demand, Harmonics,
Quality (Swell/Dip/Instantaneous Stop, Transients/Over Voltage, Inrush Current, Unbalance Rate, IEC Flicker [Pst(1 min)*, Pst, Plt]), Phase Advance Condenser
(*Pst can be shown in details for 1 minute intervals.) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Other functions |
|
|
|
Digital output function, External communication function,
Scaling function |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Voltage : |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Ranges [RMS] |
|
|
|
150 / 300 / 600 /1000V (CF: 2.5 or less, 100% or less of each range) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Allowable input |
|
|
|
10~110% of each range (1000V range : 20%~) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Display ranges |
|
|
|
5~120% of each range |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Accuracy |
|
|
|
|±0.3%rdg±0.2%f.s. (sine wave, 45~65Hz) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Current : |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Ranges [RMS] |
|
|
|
8128 ( |
50A |
type ) |
: |
1 / 5 / 10 / 20 / 50A |
8127 ( |
100A |
type ) |
: |
10 / 20 / 50 / 100A |
8126 ( |
200A |
type ) |
: |
20 / 50 / 100 / 200A |
8125 ( |
500A |
type ) |
: |
50 / 100 / 200 / 500A |
8124 ( |
1000A |
type ) |
: |
100 / 200 / 500 / 1000A |
8129 ( |
3000A |
type ) |
: |
300 / 1000 / 3000A |
(CF:3.0 or less. 90% or less of each range) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Allowable input |
|
|
|
10~110% of each range |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Display ranges |
|
|
|
1~120% of each range |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Accuracy |
|
|
|
|±0.3%rdg±0.2%f.s. + Accuracy of Clamp sensor
(sine wave, 45~65Hz) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Activa power accuracy |
|
|
|
|±0.3%rdg±0.2%f.s. + Accuracy of Clamp sensor
(Power factor 1, Sine wave, 45~65Hz) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Influence of power factor |
|
|
|
|±1.0%rdg (reading at power factor 0.5 against power factor 1) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Frequency meter range |
|
|
|
40~70Hz |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Internal memory |
|
|
|
1.8MB |
|
|
Measurement file (CSV) |
: |
256kB×6 blocks (=1.536MB) |
Screen file (BMP) |
: |
32kB×7 blocks (=0.224MB) |
Configuration file (KAS) |
: |
32kB |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Display |
|
|
|
320×240 (RGB) Pixel, 3.5-inch color STN display |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Temperature & humidity range |
|
|
|
23ºC±5ºC, Relative humidity 85% or less (no condensation) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Storage Temperature & humidity range |
|
|
|
-20ºC±60ºC, Relative humidity 85% or less(no condensation) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Operating Temperature & humidity range |
|
|
|
0ºC±40ºC, Relative humidity 85% or less(no condensation) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
PC Card type *1 |
|
|
|
Compact flash card
(Capacity: 32 / 64 / 128 / 256 / 512MB / 1 / 2 / 4 / 8GB)
* |
The CF card larger than 2GB is usable, however, the possible stored size will be limited to 2GB. For example, when the CF card of 4GB or 8GB is used, the maximum stored size will be 2GB. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Applicable standards |
|
|
|
IEC 61010-1 CAT.III 600V Pollution degree 2
IEC 61010-031, IEC 61326 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Power supply |
|
|
|
AC 100V ~ 240V±10% (45~65Hz)
Alkaline size AA battery LR6 (9V 1.5V × 6) or Ni-MH (HR15-51) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Dimension |
|
|
|
175(L)×120(W)×68(D) mm |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Weight |
|
|
|
approx. 900g (including batteries) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Accessories |
|
|
|
7141B (Voltage test lead set)
7148 (USB cable)
7170 (Power cord)
9125 (Carrying case)
8307 (Compact flash card 128MB)
8319 (CF Card reader)
Input terminal plate (6-kind)
Alkaline size AA battery (LR6) × 6
PQA MASTER (PC Software)
Quick manual
Cable marker × 32 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Optional accessories |
|
|
|
8124, 8125, 8126, 8127, 8128 (Load current clamp sensor)
8129 (Flexible clamp sensor)
8146, 8147, 8148 (Leakage & Load current clamp sensor) *2
8141, 8142, 8143 (Leakage clamp sensor) *2
8322 (Compact flash card 256MB)
8323 (Compact flash card 1GB)
8312 (Power supply adaptor)
8325F (Flicker sensor)
9132 (Carrying case (for instrument)) |
|
|
|
|
|
|
|
|
|
|
|
|